AI Performance & Benefit Evidence

Measured performance, AI-identified opportunity, actions and verified outcomes.

CURRENT FIELD STATUS

ONLINE

Last field telemetry: 2026-09-11T14:05:30.152618+05:30

Current field telemetry is reachable and fresh.

HISTORICAL EVIDENCE AVAILABILITY

Controlled optimisation history: AVAILABLE

Quality-qualified daily flow history: NOT YET PERSISTED

Evidence period:
2026-08-12 to 2026-08-20
Last field telemetry:
2026-09-11T14:05:30.152618+05:30
Data coverage:
4 controlled field tests · 2 benefit demonstrated
Evidence class:
MEASURED

Controlled field-test evidence is available. Quality-qualified historical ZTEK flow evidence is not yet persisted in the cloud. Historical source: Pilot 1 edge archive.

REPEATED CONTROLLED FIELD EVIDENCE

2 BENEFIT-DEMONSTRATION TESTS

98.1%

AVERAGE MEASURED WATER DELIVERY MAINTAINED

10.7%

AVERAGE REDUCTION IN VFD-REPORTED MOTOR LOADING

PRELIMINARY EVIDENCE

Across 2 qualifying controlled field tests, AI-Kit maintained 98.1% of measured water delivery on average while VFD-reported motor loading was 10.7% lower on average. Results remain preliminary.

Qualifying controlled tests

20 Aug 2026

BENEFIT DEMONSTRATED

Recommended frequency: 33 Hz

98.3% measured water delivery maintained · 7.9% lower VFD-reported motor loading

12 Aug 2026

BENEFIT DEMONSTRATED

Recommended frequency: 32.5 Hz

97.9% measured water delivery maintained · 13.5% lower VFD-reported motor loading

Excluded tests

19 Aug 2026

ABORTED

Control fault · Excluded from aggregate

15 Aug 2026

INCONCLUSIVE

Solar variation prevented reliable comparison · Excluded from aggregate

Long-term VERIFIED AI BENEFIT: NOT YET ESTABLISHED.

OBSERVED PERFORMANCE

Measured electrical performance available when telemetry is current

AI OPPORTUNITY IDENTIFIED

AI frequency opportunity requires a comparable valid-flow window

VERIFIED AI BENEFIT

NOT YET ESTABLISHED

Last 10 Days — Benefit Evidence

Up to 10 recent calendar days supported by authoritative history. Missing days are not fabricated.

Evidence period:
2026-08-12 to 2026-09-11
Days with valid evidence:
4/10
Coverage:
40%
DateOperating HoursObserved PerformanceExpected PerformanceAI / Test ActionOutcomeEvidence Result
11 Sept 2026

UNAVAILABLE

Measured flow absent; estimated flow retained separately and not substituted

UNAVAILABLE

No authoritative expected-flow value supplied

Review AI frequency recommendation: 33.5 Hz

NOT APPLIED · RECOMMENDED

UNAVAILABLE

No comparable expected-flow window

Opportunity cannot be quantified from one instantaneous sample.

UNAVAILABLE

Why? / Evidence
  • VFD frequency and electrical telemetry are measured.
  • Measured flow is not replaced by the available estimate.
  • Estimated flow (136.43636363636364 LPM) remains separate from measured evidence.
  • Frequency-write capability has been validated, but this record does not prove that an AI action was executed.
  • Remote START/STOP is not represented as verified.
AI recommendation
Review AI frequency recommendation: 33.5 Hz
Actually executed?
No
What happened afterward?
No qualifying before/after outcome evidence
Data quality
No valid NORMAL measured-flow evidence is available for a quantitative daily claim.
Confidence basis
90% · Existing AI recommendation confidence; not benefit verification
20 Aug 2026

33.5 Hz · 194.6 LPM · 75.5% motor load

MEASURED

Pilot 1 historical VFD/operating data and quality-qualified ZTEK flow

33 Hz · 191.3 LPM · 69.5% motor load

MEASURED

Controlled optimisation comparison

Controlled test: 33.5 Hz → 33 Hz

APPLIED · INTERVENTION

98.3% water maintained · 7.9% lower VFD-reported motor loading

MEASURED

75.5% → 69.5% motor loading; 194.6 → 191.3 LPM

98.3% water maintained during the controlled setpoint comparison.

BENEFIT DEMONSTRATED

Why? / Evidence
  • Measured water delivery was maintained while VFD motor loading was reduced under comparable solar conditions.
  • PRELIMINARY CONTROLLED FIELD EVIDENCE
  • Historical source: Pilot 1 edge archive
AI recommendation
Controlled test: 33.5 Hz → 33 Hz
Actually executed?
Yes — execution evidence recorded
What happened afterward?
98.3% water maintained · 7.9% lower VFD-reported motor loading
Data quality
Comparable controlled field evidence.
19 Aug 2026

Controlled test record

MEASURED

Pilot 1 historical VFD/operating data and quality-qualified ZTEK flow

Reliable comparison unavailable

UNAVAILABLE

Controlled optimisation comparison

Controlled test aborted after control fault

NOT APPLIED · INTERVENTION

UNAVAILABLE

Controlled optimisation history

No headline benefit contribution.

ABORTED

Why? / Evidence
  • Control fault and known transient UNDER/0 issue.
  • No benefit/loss headline contribution.
  • Historical source: Pilot 1 edge archive
AI recommendation
Controlled test aborted after control fault
Actually executed?
No
What happened afterward?
No qualifying before/after outcome evidence
Data quality
Control fault and known transient UNDER/0 issue.
15 Aug 2026

Measured baseline: 202.6 LPM

MEASURED

Pilot 1 historical VFD/operating data and quality-qualified ZTEK flow

Reliable comparison unavailable

UNAVAILABLE

Controlled optimisation comparison

Controlled comparison attempted

NOT APPLIED · INTERVENTION

UNAVAILABLE

Controlled optimisation history

No headline benefit contribution.

INCONCLUSIVE

Why? / Evidence
  • Solar irradiance varied too much during the test for a reliable frequency comparison.
  • No benefit/loss headline contribution.
  • Historical source: Pilot 1 edge archive
AI recommendation
Controlled comparison attempted
Actually executed?
No
What happened afterward?
No qualifying before/after outcome evidence
Data quality
Solar variation prevented reliable comparison.
12 Aug 2026

33.5 Hz · 243.7 LPM · 86% motor load

MEASURED

Pilot 1 historical VFD/operating data and quality-qualified ZTEK flow

32.5 Hz · 238.6 LPM · 74.4% motor load

MEASURED

Controlled optimisation comparison

Controlled test: 33.5 Hz → 32.5 Hz

APPLIED · INTERVENTION

97.9% water maintained · 13.5% lower VFD-reported motor loading

MEASURED

86% → 74.4% motor loading; 243.7 → 238.6 LPM

97.9% water maintained during the controlled setpoint comparison.

BENEFIT DEMONSTRATED

Why? / Evidence
  • Measured water delivery was maintained while VFD motor loading was reduced under comparable solar conditions.
  • PRELIMINARY CONTROLLED FIELD EVIDENCE
  • Historical source: Pilot 1 edge archive
AI recommendation
Controlled test: 33.5 Hz → 32.5 Hz
Actually executed?
Yes — execution evidence recorded
What happened afterward?
97.9% water maintained · 13.5% lower VFD-reported motor loading
Data quality
Comparable controlled field evidence.

Evidence classifications

MEASURED
Direct field sensor, VFD or RMS telemetry.
MODELLED
Calculated from an existing trained or authoritative model.
ESTIMATED
Indirectly calculated because direct instrumentation is absent.
VERIFIED
Outcome supported by an executed intervention and before/after evidence.
DATA REVIEW
Anomaly, inconsistency or insufficient data makes the result unsuitable for a benefit claim.
UNAVAILABLE
Required evidence does not exist.

Opportunity is never counted as verified benefit unless an intervention was executed and supported by before/after outcome evidence.