Current AI assessment

REVIEW

Water delivery needs attention.

Water delivery is persistently below the learned healthy baseline.

What should I do?

Recommended action

Inspect the discharge path, water source and pump-side hydraulic condition. Possible causes include pump-side restriction, source-water condition, piping condition, or hydraulic degradation; current instrumentation cannot isolate the exact physical cause.

Motor Electrical

NORMAL

Current: 12.3 A · Output voltage: 332.7 V · Power / load: 4.8 kW · Frequency: 44 Hz

Available motor electrical measurements are consistent with the current operating state.

MEASURED

VFD / Drive

NORMAL

DC bus: 561.4 V · Output voltage: 332.7 V · Output frequency: 44 Hz · Fault state: NO FAULT

No active drive fault or inconsistent output is present in the latest sample.

MEASURED

Water Delivery

REVIEW

Actual 183.2 LPM · Expected 201.4 LPM · Performance 91%

Water delivery is persistently below the learned healthy baseline.

AUTHORITATIVE AI + MEASURED

AI / Predictive Performance

REVIEW

Existing authoritative score: 91/100

Water output is slightly below the learned healthy baseline. Continue monitoring for persistent deviation.

AUTHORITATIVE AI

Predictive Pump & Water Intelligence

Water Performance
91%
Water Today
88.7 m³
Tomorrow Expected
154.7 m³
Early Warning
WATCH
View Trends →
Why does AI-Kit say this?
  • Available motor electrical measurements are consistent with the current operating state.
  • No active drive fault or inconsistent output is present in the latest sample.
  • Water delivery is persistently below the learned healthy baseline.
  • Frequency, load and flow remain consistent with the learned healthy operating relationship.
Technical details

Marker evidence basis

Motor Electrical · STATE CONSISTENCY
MEASURED · Current: 12.3 A · Output voltage: 332.7 V · Power / load: 4.8 kW · Frequency: 44 Hz
VFD / Drive · FAULT STATE
MEASURED · DC bus: 561.4 V · Output voltage: 332.7 V · Output frequency: 44 Hz · Fault state: NO FAULT
Water Delivery · MODEL EXPECTATION
AUTHORITATIVE AI + MEASURED · Operating samples: 47 · Model: Expected Flow AI · Basis: Pilot-2 learned healthy operating behaviour
AI / Predictive Performance · LEARNED BASELINE
AUTHORITATIVE AI · Performance: 91% · Trend: DECLINING

Monitored Subsystem Health

What current evidence supports

Motor Electrical Performance

HEALTHY

Available motor electrical measurements are consistent with the current operating state.

  • Current: 12.3 A
  • Output voltage: 332.7 V
  • Power / load: 4.8 kW
  • Frequency: 44 Hz

Recommended action

Continue monitoring electrical operating consistency.

Monitoring scope: Electrical operating assessment; not a bearing, winding-temperature or insulation diagnosis

Provenance: MEASURED

VFD / Drive Health

HEALTHY

No active drive fault or inconsistent output is present in the latest sample.

  • DC bus: 561.4 V
  • Output voltage: 332.7 V
  • Output frequency: 44 Hz
  • Fault state: NO FAULT

Recommended action

Continue monitoring the drive fault state and output consistency.

Monitoring scope: Latest VFD telemetry; historical fault continuity is not supplied by this preview source

Provenance: MEASURED

Hydraulic Performance

REVIEW

Water delivery is persistently below the learned healthy baseline.

  • Water performance: 91%
  • Actual vs expected flow: 183.2 LPM vs 201.4 LPM
  • Persistent low days: 0
  • Recent trend: DECLINING

Recommended action

Inspect the discharge path, water source and pump-side hydraulic condition. Possible causes include pump-side restriction, source-water condition, piping condition, or hydraulic degradation; current instrumentation cannot isolate the exact physical cause.

Monitoring scope: Indirect hydraulic assessment; does not identify a specific internal component fault

Provenance: INDIRECT

Pump Performance

HEALTHY

Frequency, load and flow remain consistent with the learned healthy operating relationship.

  • Model: Expected Flow AI flow-v2
  • Basis: Pilot-2 learned healthy operating behaviour
  • Operating samples: 47
  • Performance: 91%

Recommended action

Continue baseline comparison under comparable operating conditions.

Monitoring scope: Indirect pump-level performance assessment; not an impeller, seal or bearing diagnosis

Provenance: AUTHORITATIVE AI

RMS / Communications

HEALTHY

RMS signal and latest-sample freshness are acceptable.

  • RMS signal: 74%
  • Sample age: 0 min
  • RMS temperature: 61.4 °C
  • Telemetry gap history: not available from the current source

Recommended action

Continue monitoring signal and sample freshness.

Monitoring scope: Communications assessment from the latest sample; continuity gaps cannot be confirmed without history

Provenance: TELEMETRY

Monitoring limits

What is not directly monitored

AI-Kit can detect changes in monitored operating behaviour, but current instrumentation cannot always identify the exact physical component responsible. These coverage labels are not faults.

Motor Bearings

NOT INSTRUMENTED

No dedicated vibration or bearing-temperature measurement.

Motor Winding Temperature / Insulation

NOT DIRECTLY MONITORED

Only indirect electrical indicators are available.

Pump Seal

NOT INSTRUMENTED

No leakage, pressure, or seal-specific sensor.

Impeller

INDIRECT ASSESSMENT

Hydraulic degradation may be detected, but current sensors cannot uniquely identify impeller wear.

Model and data context

Predictive Pump & Water Intelligence with clear boundaries between measured, inferred, and uninstrumented conditions.

Telemetry history: live.